Inspection
Inspection Details
Equipment ID
18677
18677
Inspection Date
3/20/2019
3/20/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
20
20
External ID
10e30719-e907-47f5-bded-190638bfa1f0
10e30719-e907-47f5-bded-190638bfa1f0
Location
Syndicate Apartments
915 OLIVE ST, SAINT LOUIS, MO
915 OLIVE ST, SAINT LOUIS, MO
Owner
Attn: Brendan Kinney
Syndicate Building
915 OLIVE ST, SAINT LOUIS, MO 63101
Phone: (314) 249-9896
Fax: (314) 454-1556
Syndicate Building
915 OLIVE ST, SAINT LOUIS, MO 63101
Phone: (314) 249-9896
Fax: (314) 454-1556
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 6/16/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance control program. | 6/16/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete. Inspected hoistway, elevator pit, tested phase I and II fire service, tested cab phone, emergency lights and alarm bell | 9/19/2023 |
| A17.1-1996 : Elevators | 2.29 - Car and counterweight safeties | Table 205.3 | Yes | Yes | Elevator car safeties are stopping the car too fast with the rated load. Slide shall be no less than 13 inches. Current slide is 8 inches. Red tag | 9/20/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work, needs repaired. Re-inspection required | 4/16/2025 |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean dirt & debris from elevator car top | 4/24/2026 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.6.3.2 (Re-Inspection) | Yes | Yes | Elevator suspension cables are severely rouged and many layers have gaps between adjacent layers showing signs of internal breakage.. Red-tagged, removed from service. Re-inspection required | 4/24/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | Yes | No | Isolation pads under suspension cable shackle springs in the machine room are either deteriorated or missing. Replace isolation pads. Re-inspection required | 4/24/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work, needs repaired. Re-inspection required | 4/24/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work, needs repaired. Re-inspection required |