Inspection
Inspection Details
Equipment ID
24578
24578
Inspection Date
4/3/2019
4/3/2019
Inspection Type
New Installation
New Installation
Inspector Name
Conde (Cache) Kinsella
Conde (Cache) Kinsella
Mechanic Name
Benjamin Postawko
Benjamin Postawko
Relief Valve Pressure
Slide
Inst
Inst
Governor Rope Pull
30/179
30/179
Door Closing Force
25/28
25/28
External ID
9e2189f6-b4f0-40a4-b6ad-2f518135e87e
9e2189f6-b4f0-40a4-b6ad-2f518135e87e
Location
B'nai B'rith Covenant House, Inc
8 Millstone Campus Dr, St. Louis, MO
Phone: (314) 432-1610
8 Millstone Campus Dr, St. Louis, MO
Phone: (314) 432-1610
Owner
B'nai B'rith Covenant House, Inc
8 MILLSTONE CAMPUS DR STE 200, SAINT LOUIS, MO 63146-5766
8 MILLSTONE CAMPUS DR STE 200, SAINT LOUIS, MO 63146-5766
Billing
Attn: Community Housing Mgmt Corp
8 MILLSTONE CAMPUS DR STE 200, SAINT LOUIS, MO 63146-5766
8 MILLSTONE CAMPUS DR STE 200, SAINT LOUIS, MO 63146-5766
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 9/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 9/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire Service testing must be properly documented monthly on Log Sheet. | 7/12/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | In car emergency lighting shall work. | 3/28/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency lights shall be operational. (2nd Notice) | 7/25/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1, with the identification of the person(s) that performed the operation and the date shall be available on site. | 5/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | A capacity plate listing the capacity in pounds shall be provided and prominently displayed in the car enclosure. | 5/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The unique car identification shall be provided and displayed on the car operating panel. | 5/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room in a noncombustible frame with a clear protective vision plate over it. | 5/1/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)9 Capacity Plate | No | No | Car capacity plate is missing. | 10/31/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency lights shall be operational. This is the 3rd and final notice regarding this violation. Failure to correct this violation will result in the elevator being locked out of service until corrected. | 10/31/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator equipment room in a noncombustible frame with a clear protective vision plate over it. |