Inspection
Inspection Details
Equipment ID
18997
18997
Inspection Date
4/1/2019
4/1/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
24
24
External ID
4d2a8ee0-e4ec-4148-8e39-a3fbe69be1e9
4d2a8ee0-e4ec-4148-8e39-a3fbe69be1e9
Location
Iatan Station
20256 STATE ROUTE 45 N, WESTON, MO
20256 STATE ROUTE 45 N, WESTON, MO
Owner
Attn: UNK
KC Power & Light
1201 WALNUT, KANSAS CITY, MO 64141
Phone: (000) 000-0000
Email: lynette.hurst@kcpl.com
KC Power & Light
1201 WALNUT, KANSAS CITY, MO 64141
Phone: (000) 000-0000
Email: lynette.hurst@kcpl.com
Billing
Attn: UNK
Iatan Power Plant
20250 STATE ROUTE 45 N, WESTON, MO 64098
Phone: (000) 000-0000
Email: acctspay@kcpl.com
Iatan Power Plant
20250 STATE ROUTE 45 N, WESTON, MO 64098
Phone: (000) 000-0000
Email: acctspay@kcpl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | No | No | Provide code data plate and display on disconnect or controller. | 9/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Machine room light fixture is extremly dim. Need to provide a minimum of 10 ft candles of illumination at machine room floor. | 8/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | No | No | Need to provide code data plate and display on disconnect or controller. | 8/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not call out. | 5/13/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Test and log firefighter operation monthly | 3/4/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Post emergency evacuation of passengers procedure in machine room | 3/4/2023 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.6.4.20.11 (Re-Inspection) | Yes | No | Provide emergency brake for ascending car and unintended motion protection. | 5/13/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | No | No | Provide firefighter cabinet on car operating panel | 5/13/2022 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.6.4.20.11 (Re-Inspection) | Yes | No | Provide emergency brake for ascending car and unintended motion protection | 5/22/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | Yes | No | Provide firefighter cabinet on car operating panel | 5/22/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | Maintenance record log not up to date | 9/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current state operating certificate not displayed | 9/16/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Repair the pit light. | 8/5/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove the water from the pit. | 8/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone. | 4/30/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide machine room lighting. | 8/5/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove the water from the pit | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone |