Inspection
Inspection Details
Equipment ID
14619
14619
Inspection Date
3/29/2019
3/29/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Justin Kennedy
Justin Kennedy
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
355c969f-9ed0-4ca5-9b23-a7122a2af0ea
355c969f-9ed0-4ca5-9b23-a7122a2af0ea
Location
Chilton Place Apts
415 N 10TH ST, SAINT JOSEPH, MO
415 N 10TH ST, SAINT JOSEPH, MO
Owner
Community Housing Ministries
730 S 6TH ST, SAINT JOSEPH, MO 64501-2228
730 S 6TH ST, SAINT JOSEPH, MO 64501-2228
Billing
Attn: Community Housing Ministries
730 S 6TH ST, SAINT JOSEPH, MO 64501-2228
730 S 6TH ST, SAINT JOSEPH, MO 64501-2228
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency phone and emergency light do not operate. | 4/15/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside the machine room | 5/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 4/14/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove scavenger pump from pit. Cylinder drain line needs to drain into pit collection container of no more than 5 gallons | 5/10/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 5/31/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove scavenger pump from pit | 5/10/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No current state operating certificate displayed, or on site. | 5/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emegency phone dials out. Can not hear anyone on the other end. Bad phone or speaker volume on phone needs to be increased | 12/15/2022 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | Test emergency fire recall alarm initiating devices | 12/21/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(d) | Yes | No | Post metal permanent record of acceptance test on controller | 12/21/2023 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | Machine room fire alarm initiating device does not recall elevator. Retest machine room fire alarm initiating device. | 12/22/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit has oil on floor needs to be cleaned | 12/12/2024 |