Equipment ID
13727
13727
Inspection Date
3/29/2019
3/29/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
Na
Na
Door Closing Force
NA
NA
External ID
45aff07b-ac55-43a3-98c1-0f7dd9203e78
45aff07b-ac55-43a3-98c1-0f7dd9203e78
Location
AT & T - One Bell Center
1010 PINE ST, SAINT LOUIS, MO
1010 PINE ST, SAINT LOUIS, MO
Owner
Attn: AT&T Certificate MGMT c/o Lerch Bates
AT&T Certificate MGMT c/o Lerch Bates
9780 S. Meridian Blvd, Ste 450, Englewood, CO 80112
Phone: (303) 795-7956
Email: Att.elevators@lerchbates.com
AT&T Certificate MGMT c/o Lerch Bates
9780 S. Meridian Blvd, Ste 450, Englewood, CO 80112
Phone: (303) 795-7956
Email: Att.elevators@lerchbates.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Provide Emergency Phone | 3/29/2019 |
| A17.1-1996 : Elevators | 4.4 - Hoistway door locking devices | 111 | Yes | No | Interlock cover on the 17th floor missing. | 7/27/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 7/27/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 2/24/2021 |
| A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | No | No | Replace missing door close button tactile plate in car operating panel. | |
| A17.1-1996 : Elevators | 3.20 - Governor rope | 1001.2(c)(26) | Yes | Yes | Overspeed governor rope tension sheave is bottomed out. Shorten governor rope. Red tagged. | 2/24/2021 |
| A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | No | No | Replace missing door close button tactile plate in car operating panel. | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 9/2/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace missing tactile plate on COP | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Replace CO2 fire extinguishers with ABC type. Both elevator machine room and secondary spaces. | |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Provide existing emergency lights and bell to work. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing pull straps (3), floors 2B,S,1.. hoistway doors. | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Provide testing of the elevator on emergency power. | |
| A17.1-1996 : Elevators | 4.12 - Standby power selection switch | 1001.2(d)(12) | Yes | No | Provide testing of the elevator emergency power selector switch (fire command room). |