Inspection
Inspection Details
Equipment ID
10700
10700
Inspection Date
3/29/2019
3/29/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
38
38
Governor Rope Pull
50/640
50/640
Door Closing Force
26
26
External ID
4d87a3a7-b8f4-4c6a-ad89-300275dfa489
4d87a3a7-b8f4-4c6a-ad89-300275dfa489
Location
Parkview Elderly Apts
4451 FOREST PARK AVE, SAINT LOUIS, MO
Phone: (314) 533-3350
4451 FOREST PARK AVE, SAINT LOUIS, MO
Phone: (314) 533-3350
Owner
Attn: Sontez Singleton
The Habitat Company
4451 FOREST PARK AVE, SAINT LOUIS, MO 63108
Phone: (314) 533-3350
Email: ssingleton@habitat.com
The Habitat Company
4451 FOREST PARK AVE, SAINT LOUIS, MO 63108
Phone: (314) 533-3350
Email: ssingleton@habitat.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Pits shall be clean | 5/9/2019 |
| conversion | conversion | n/a | No | No | Emergency phone not working | 5/9/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Cab lighting needs to be guarded. | 5/9/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | Car door restrictor does not work. | 5/7/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean elevator pit. | 7/21/2020 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are below minimum diamter. | 5/12/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Written maintenance control program shall be kept on site for each elevator. | 6/15/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | All pits shall be kept dry & clean and free of equipment or material not relating to the operation of the elevator | 3/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A MCP shall be provided for each unit and kept on site | 3/26/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator was not running at scheduled test date. Repair elevator and perform annual no load test of elevator. | 1/5/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency generator test needs to be witnessed when all Modernizations are completed. | 5/27/2025 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | After the third car modernization is finished, all covers on electrical boxes shall be installed. | 5/27/2025 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | All cross wiring connections shall be complete. | 5/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Elevator cab must have a permanent slip resistant floor installed. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Machine room door must be self-closing and self-locking | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power must be tested annually. |