Inspection
Inspection Details
Equipment ID
13305
13305
Inspection Date
4/8/2019
4/8/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jeffrey Krug
Jeffrey Krug
Mechanic Name
David Baybo
David Baybo
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
n/a
n/a
External ID
74f1dc40-fb42-41f4-9b20-4f801430e273
74f1dc40-fb42-41f4-9b20-4f801430e273
Location
St. Louis County
100 S CENTRAL AVE, CLAYTON, MO
100 S CENTRAL AVE, CLAYTON, MO
Owner
Attn: St. Louis County Transportation/Public Works Dept
St. Louis County Transportation/Public Works Dept
1050 N Lindbergh Blvd, Creve Coeur, MO 63132
Phone: (314) 645-2277
Email: cmacdonald@richmondheights.org
St. Louis County Transportation/Public Works Dept
1050 N Lindbergh Blvd, Creve Coeur, MO 63132
Phone: (314) 645-2277
Email: cmacdonald@richmondheights.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.7.1.8 | Yes | No | A data plate shall be provided as required by 8.6.1.5. In jurisdictions enforcing NBCC, the data plate required by 8.9.1 shall include the code and edition in effect at the time of alteration and the requirements in Section 8.7 that were applicable to the alteration. | 4/23/2026 |
| A17.1-2016 : Elevators | 2.30 - Hydraulic Power Unit | 8.10.3.3.2(p) | Yes | No | 8.7.3.31.5(c)(8) The elevator identification needs to be labeled on on both doorjambs of every elevator entrance at the designated level, alternate level, level where means necessary for tests is provided, and the driving machine. | 4/23/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Pipes conveying liquid, gas, or vapor that cross overhead of elevator equipment or come in close proximity of the equipment shall be guarded or guttered. | 4/23/2026 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 3.8 | Yes | No | 8.7.3.8 The hydraulic line cannot be located in front the controller. Then area in front of the controller needs to be clear from the floor to the top of the controller 36" deep and 30" wide. | 4/23/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.10.3.3.2(l) | Yes | No | Need to test the operation of emergency power. | 4/23/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | Yes | No | 8.7.3.31.5(c)(7) "ELEVATOR COMMUNICATIONS FAILURE" feature needs to be provided to verify operability of the telephone line. | 4/23/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.19.15 Emergency Communications | Yes | No | 8.7.3.31.5(c)(7)A visual indication on the same panel as the “PHONE” push button shall be provided, that is activated by authorized personnel, to acknowledge that two-way communications link has been established. | 4/23/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.10.2.3.2(l) | Yes | No | Need to test the operation of emergency power with full capacity in the elevator. Emergency power was not tested during the acceptance. | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | No | No | "ELEVATOR COMMUNICATIONS FAILURE" feature needs to be provided to verify operability of the telephone line. | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.19.15 Emergency Communications | Yes | No | A visual indication on the same panel as the “PHONE” push button shall be provided, that is activated by authorized personnel, to acknowledge that two-way communications link has been established. |