Inspection
Inspection Details
Equipment ID
7663
7663
Inspection Date
3/27/2019
3/27/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
0211e2a7-ea37-4238-950c-5e15a1377027
0211e2a7-ea37-4238-950c-5e15a1377027
Location
Humboldt Bldg
539 N GRAND BLVD, SAINT LOUIS, MO
539 N GRAND BLVD, SAINT LOUIS, MO
Owner
Fox Associates
527 N GRAND BLVD, SAINT LOUIS, MO 63103-1006
527 N GRAND BLVD, SAINT LOUIS, MO 63103-1006
Billing
Attn: Fox Associates
527 N GRAND BLVD, SAINT LOUIS, MO 63103-1006
527 N GRAND BLVD, SAINT LOUIS, MO 63103-1006
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | Repair machine room lights. | 5/12/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell does not work on emergency 110v power or normal power | 12/30/2021 |
| A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 1001.2(e)(10) | Yes | Yes | Safety Operated Switch attached to governor rope is broken and not operable. RED TAG | 12/30/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection is incomplete, must complete all weight testing and spinning the governor. Spring buffers do not need compressed. | 12/30/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Brake failed to hold capacity load. Car removed from service. | 2/11/2022 |
| A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 205.11 | Yes | Yes | Car safety wind up drum cable had 2 wraps left on the drum after setting the safeties. Repair or replace cable or safeties | 3/24/2022 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Fire extinguisher in machine room is expired, needs serviced or replaced | 12/7/2022 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.1 | No | No | Machine room 110 supply shall be installed to the NFPA 70 with receptacle box mounted securely to the wall | 12/7/2022 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 100 | No | No | Patch/repair all holes in the hoistway walls. Hole in hoistway wall about 8' to 10' looking through to the back of interior sheet rock office wall. Also, other smaller holes. | 3/1/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency alarm bell shall be operational. | 2/21/2024 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 100 | Yes | No | Holes need to be patched in hoistway. (Repeat Violation) Re-Inspection required. | 4/8/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency alarm bell shall be operational. (Repeat Violation) Re-Inspection required. | 4/8/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency alarm bell shall be operational. (Final Notice) This violation shall be corrected immediately or the unit will be red tagged out of service until corrected. | 3/1/2026 |
| A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 203 | Yes | Yes | SOS switch shall be operational. Elevator left down/out of service. | 3/1/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/1/2026 |