Inspection
Inspection Details
Equipment ID
18666
18666
Inspection Date
3/26/2019
3/26/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
27
27
External ID
ddf3ffaf-6201-47c0-8e38-afb6fae03290
ddf3ffaf-6201-47c0-8e38-afb6fae03290
Location
AmeriStar Casino
1 AMERISTAR BLVD, SAINT CHARLES, MO
1 AMERISTAR BLVD, SAINT CHARLES, MO
Owner
Attn: UNK
AmeriStar Casino- St. Charles LLC
1260 S MAIN ST, SAINT CHARLES, MO 63301
Phone: (000) 000-0000
AmeriStar Casino- St. Charles LLC
1260 S MAIN ST, SAINT CHARLES, MO 63301
Phone: (000) 000-0000
Billing
Attn: AmeriStar Casino- St. Charles, LLC
AmeriStar Casino- St. Charles LLC
1 AMERISTAR BLVD, SAINT CHARLES, MO 63301
Phone: (000) 000-0000
Email: PatMcdonald@boydgaming.com
AmeriStar Casino- St. Charles LLC
1 AMERISTAR BLVD, SAINT CHARLES, MO 63301
Phone: (000) 000-0000
Email: PatMcdonald@boydgaming.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | Yes | Upon performing the required five year full load, the elevator safety governor was found to be worn to a degree that the pull-through force was overly excessive and could potentially permanently damage the elevator safeties if testing proceeded. The elevator has been removed from service. Repair or replacement of the governor is required and a reinspection shall be performed before the elevator can be returned to service. | 1/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The emergency light fixture inside the elevator is not operational and shall be repaired. Reinspection required. | 1/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | No | No | The hoistway door retaining gib on the hoistway door is missing on the 7th floor. Reinstall missing gib to retain the hoistway door in the sill properly. | 7/27/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | The testing has not been completed on the elevator at this time, the elevator was placed out of service due to governor failure. The weight test shall be performed, safeties set, and buffers compressed before the inspection is completed. | 1/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 7/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Provide existing emergency lights to work | 2/15/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 7/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 4/10/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | There are a number of machine room lighting fixtures that are not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | 3/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The emergency rescue battery in the controller has not been changed since 2019. The manufacture’s recommendation for replacement is 3 years. Replacement of the battery before the elevator shuts down due to battery being depleted is required. | 3/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.8.4 | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 7/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Perform the required Cat 1 testing of the emergency generator | 2/10/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 6/15/2025 |