Equipment ID
11222
11222
Inspection Date
4/9/2019
4/9/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Vernon Livergood
Vernon Livergood
Mechanic Name
Korey Luttrell
Korey Luttrell
Relief Valve Pressure
Slide
00
00
Governor Rope Pull
000
000
Door Closing Force
00
00
External ID
0dd20f93-58a9-4df4-904c-18f6f9660a03
0dd20f93-58a9-4df4-904c-18f6f9660a03
Location
Jackson County Courthouse
415 E 12TH ST, KANSAS CITY, MO
415 E 12TH ST, KANSAS CITY, MO
Owner
Attn: UNK
Jackson Co Courthouse Facilities Mgmt
415 E 12TH ST, KANSAS CITY, MO 64106
Phone: (000) 000-0000
Email: Bgaddie@jacksongov.org
Jackson Co Courthouse Facilities Mgmt
415 E 12TH ST, KANSAS CITY, MO 64106
Phone: (000) 000-0000
Email: Bgaddie@jacksongov.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Main hoisting ropes undersized. Min.469 actual .460 | 4/9/2019 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Emergency lights not working. | 6/29/2021 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Emergency alarm not working. | 6/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | All landing doors need maintenance, and adjustments. Rollers, upthrusts, eccentrics, etc. | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices | Yes | Yes | Supply test of fire alarm devices | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 8.11.2.1.3(p) | Yes | No | seal voids and penetrations in hoistway | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 8/30/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | Yes | No | Provide an audible signal while in recall. | 5/19/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | Provide an audible signal during recall. | 5/22/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Repair the pit lighting. | 5/22/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone. |