Inspection
Inspection Details
Equipment ID
19532
19532
Inspection Date
4/8/2019
4/8/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
William Gorden, Jr.
William Gorden, Jr.
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
26
26
External ID
41f38a04-6385-43f9-8067-d85eb3b3a7fc
41f38a04-6385-43f9-8067-d85eb3b3a7fc
Location
The Cresent
153 CARONDELET PLZ, CLAYTON, MO
153 CARONDELET PLZ, CLAYTON, MO
Owner
The Crescent Condominium
155 CARONDELET PLZ STE 100, CLAYTON, MO 63105-3479
155 CARONDELET PLZ STE 100, CLAYTON, MO 63105-3479
Billing
Attn: The Crescent Condominium C/O Community Property Mgmt
242 OLD SULPHUR SPRING RD, MANCHESTER, MO 63021-5353
242 OLD SULPHUR SPRING RD, MANCHESTER, MO 63021-5353
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 4.5 - Access to Hoistway | 1001.2(d)(5) | No | No | The hoistway door access key switch plate on the bottom landing is broken and shall be repaired to operate as designed. | 8/10/2020 |
| A17.1-1996 : Elevators | 4.5 - Access to Hoistway | 1001.2(d)(5) | No | No | The hoistway door access key switch plate on the bottom landing is broken and shall be repaired to operate as designed. | 8/10/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: Phase II did not initiate when the fireman's emergency service key was turned to the “ON” position. Reinspection is required. | 4/27/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | Yes | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: Phase II did not initiate when the fireman's emergency service key was turned to the “ON” position. The unit is locked out of service until it is repaired and a reinspection has been performed. | 5/1/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance control program. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Clean pit. | |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 1001.2(c)(2) | No | No | Car top outliet has neutral reversed. Repair as needed. | |
| A17.1-1996 : Elevators | 2.17 - Drive machine brake | 1001.2(b)(15) | Yes | Yes | Car does not have emergency brake cable system. Provide and retest. | 7/5/2022 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 1001.2(b)(4) | No | No | Top of hoistway stop switch missing cover. | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Replace or service fire extinguisher in control room. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Category 5 testing needs to be completed, was only able to conduct annual portion of test. | 7/21/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room |