Inspection
Inspection Details
Equipment ID
2021
2021
Inspection Date
3/15/2019
3/15/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Richard Toeniskoetter
Richard Toeniskoetter
Relief Valve Pressure
490
490
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
da1a1009-54e1-4abb-9e72-1a2a1087f5df
da1a1009-54e1-4abb-9e72-1a2a1087f5df
Location
South High School
8050 MEXICO RD, SAINT PETERS, MO
8050 MEXICO RD, SAINT PETERS, MO
Owner
Ft. Zumwalt School District
840 LONE STAR DR, O FALLON, MO 63366-1950
840 LONE STAR DR, O FALLON, MO 63366-1950
Billing
Attn: Ft. Zumwalt School District
840 LONE STAR DR, O FALLON, MO 63366-1950
840 LONE STAR DR, O FALLON, MO 63366-1950
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work. | 3/29/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 6/15/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. Clean the oil from the pit. | 6/15/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/15/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 4/16/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone. | 6/24/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in-car alarm bell shall be operational on main and auxiliary power. | 6/24/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in-car emergency lights shall be operational. | 6/24/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The car door shall be restricted from opening more than 4" when in the closed position anywhere outside the unlocking zone. Not compliant at time of 6/24/25 re-inspection. | 7/23/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell not working. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lights not working. |