Inspection
Inspection Details
Equipment ID
23519
23519
Inspection Date
3/18/2019
3/18/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
William Gorden, Jr.
William Gorden, Jr.
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
89b489b6-c9a1-4df6-a06c-cea8f8570446
89b489b6-c9a1-4df6-a06c-cea8f8570446
Location
Watlow Electric Mfg Company
12001 LACKLAND RD, SAINT LOUIS, MO
12001 LACKLAND RD, SAINT LOUIS, MO
Owner
Watlow Electric Mfg Company
12001 LACKLAND RD, SAINT LOUIS, MO 63146-4001
12001 LACKLAND RD, SAINT LOUIS, MO 63146-4001
Billing
Attn: Watlow Electric Mfg Company
12001 LACKLAND RD, SAINT LOUIS, MO 63146-4001
12001 LACKLAND RD, SAINT LOUIS, MO 63146-4001
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | No | The means for manual release of the brakes shall be operational. | 4/20/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 8.11.2.1.5(g) | No | No | Subsequent to the first stop of the car following the opening of the tail switch tension switch, the car shall remain inoperative until the switch is manually reset. (Currently this switch opens the safety circuit, stopping the car immediately) | 7/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 2.18.5 | No | No | The governor rope shall be tagged as specified by code. | 4/20/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | Fire gibs are missing from the hoistway doors. | 4/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Fire gibs are missing from the hoistway doors. (2nd Notice) | 9/24/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | MCP fire service testing must be properly documented monthly on log sheet. | 7/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Remove construction related hoisting beams and brackets from machine room. | 7/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Fire gibs (hoistway door safety retainers) are missing from hoistway doors. (3rd Notice) - Violation shall be corrected and re-inspected or elevator will be red tagged and locked out of service for non-compliance. | 12/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 2.18.7 | Yes | No | Subsequent to the first stop of the car following the opening of the tail switch tension switch, the car shall remain inoperative until the switch is manually reset. (Currently this switch opens the safety circuit, stopping the car immediately). State of MO accidentally marked as fixed when it was not. | 5/1/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire Service shall be tested and documented monthly. | 5/1/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 5/1/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Machine room fire alarm device base is broken and hanging by its wiring. | 5/1/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire Service shall be tested and documented monthly. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. |