Inspection
Inspection Details
Equipment ID
12141
12141
Inspection Date
4/9/2019
4/9/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
39b20b64-937d-409f-b34a-fb900c2f148c
39b20b64-937d-409f-b34a-fb900c2f148c
Location
Brazilia Apartments Office Bldg
4372 CASA BRAZILIA DR, SAINT LOUIS, MO
4372 CASA BRAZILIA DR, SAINT LOUIS, MO
Owner
Brazilia Apartment Bldg Office
1194 CASA BRAZILIA CT, SAINT LOUIS, MO 63129-1814
1194 CASA BRAZILIA CT, SAINT LOUIS, MO 63129-1814
Billing
Attn: Brazilia Apartment Bldg Office
1194 CASA BRAZILIA CT, SAINT LOUIS, MO 63129-1814
1194 CASA BRAZILIA CT, SAINT LOUIS, MO 63129-1814
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | The bearings on the door operator have degraded and shall be replaced. Repair the door operator. | 7/6/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current state operating certificate shall be displayed in machine room. | 5/30/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Car ceiling panels are of the open crate type, which do not provide protection of passengers in event of bulb breakage. Replace panels with solid type or cover bulbs with plastic tubes. | 8/20/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be on display in the machine room | 5/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired, have serviced or replaced. | 8/20/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working, appears not to have a live line. Re-inspection required | 2/19/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing and self-locking and operable from the interior space without the use of a key. | 8/20/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher is expired. A current tested & tagged ABC type fire extinguisher shall be provided in the machine room. | 8/20/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/30/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. (2nd Notice) | 5/30/2025 |