Inspection
Inspection Details
Equipment ID
8331
8331
Inspection Date
6/12/2017
6/12/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
GKN Aerospace Services- Bldg 27
142 J S McDonnell Blvd, Hazelwood, MO
Phone: (314) 264-3071
142 J S McDonnell Blvd, Hazelwood, MO
Phone: (314) 264-3071
Owner
GKN Aerospace Services
142 J S McDonnell Blvd, Hazelwood, MO 63042
142 J S McDonnell Blvd, Hazelwood, MO 63042
Billing
Attn: GKN Aerospace Services
PO Box 4009, , MO 63042
PO Box 4009, , MO 63042
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | The elevator pit light switch in the pit have corroded due to the high humidity levels and is no longer reliable. Replace switch. | 8/26/2020 |
| conversion | conversion | n/a | No | No | The elevator pit stop switch in the pit have corroded due to the high humidity levels and is no longer reliable. Replace switch. | 8/26/2020 |
| conversion | conversion | n/a | No | No | The hoistway door interlock switches at the bottom landing have corroded due to the high humidity levels and are no longer reliable. Replace switches. | 8/26/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | No | No | Replace rusted pit stop switch. Piping and wiring is rusted. | 8/26/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Replace pit light switch. Rusted out. Recommend using water tight boxes and piping. | 8/26/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. | 8/28/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. | 8/28/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | Yes | Unit did not close rear doors and return to main recall landing when returning to Phase 1 operation from Phase 2. Red tagged unit. | 7/30/2021 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | Yes | car tractions before reaching top final limit switch. Red tagged. Repair same before returning to service. | 9/19/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | pit light shall work | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | perform following tests to complete inspection: fire service phase I and II, seismic (including "ring and string, which has bee bypassed as result of water in lower level previously), soft set safeties | 9/19/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | Yes | Car tractions before reaching top final limit switch. Red-tagged, Re-inspection required | 11/13/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform the following tests to complete inspection: fire service phase 1 & 2, seismic (including ring & string which has been by passed as result of water in lower level previously) soft set car safeties. | 11/13/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test car safeties (soft set). Re-inspection required | 1/26/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform test on car safeties (soft set) Re-inspection required. Tried to perform test, but elevator pit & bottom floor were underwater. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform test on car safeties (soft set) Re-inspection required. |