Inspection
Inspection Details
Equipment ID
13966
13966
Inspection Date
4/3/2019
4/3/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
600
600
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
27
27
External ID
ce351b50-efbc-4899-9d94-18219a31dce5
ce351b50-efbc-4899-9d94-18219a31dce5
Location
Majestic Lofts
2020 DELMAR BLVD, SAINT LOUIS, MO
2020 DELMAR BLVD, SAINT LOUIS, MO
Owner
Robert Wood Realty
2020 DELMAR BLVD, SAINT LOUIS, MO 63103-1655
2020 DELMAR BLVD, SAINT LOUIS, MO 63103-1655
Billing
Attn: Majestic Stove Lofts
2020 DELMAR BLVD, SAINT LOUIS, MO 63103-1655
2020 DELMAR BLVD, SAINT LOUIS, MO 63103-1655
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work | 8/25/2020 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone line is not working. Re-inspection required | 7/11/2022 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Phone not working correctly. | 9/22/2022 | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | Phase II signage is missing in car, replace. | 6/26/2023 | ||
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 100 | Hoistway wall (rear) is damaged near 2nd floor, repair needed. | 6/26/2023 | ||
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(4) | x | Right jack has return line going back to tank, remove. | 6/19/2023 | |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | Provide means to collect oil from right jack, to be kept in the pit. | 6/26/2023 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | Sump hole is filled with oil, remove. | 6/26/2023 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | Determine if the sump pump is working correctly, if not then replace. | 6/26/2023 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | The directional arrow cover on the left side of the entrance shall be replaced | |||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | The emergency phone shall be made operational. Re-inspection required | ||
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | x | Emergency lowering is not working properly. Re-inspection required |