Inspection
Inspection Details
Equipment ID
14577
14577
Inspection Date
4/8/2019
4/8/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Kevin Liles
Kevin Liles
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
38dbde42-3ac3-48b8-abac-a76f6b2825bf
38dbde42-3ac3-48b8-abac-a76f6b2825bf
Location
Boeing Bldg #106
6300 JAMES S MCDONNELL BLVD, BERKELEY, MO
6300 JAMES S MCDONNELL BLVD, BERKELEY, MO
Owner
Boeing Co
PO BOX 516, SAINT LOUIS, MO 63166-0516
PO BOX 516, SAINT LOUIS, MO 63166-0516
Billing
Attn: Boeing Co
PO BOX 516, SAINT LOUIS, MO 63166-0516
PO BOX 516, SAINT LOUIS, MO 63166-0516
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell not working on emergency power | 7/31/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)5 | Yes | Yes | Gat switch not working red tagged out of service | 7/31/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Full load overspeed vlave test past due 90 day max on completing test | 8/23/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 12/15/2025 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | Yes | No | Machine room is missing GFCI. | 7/22/2025 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.7.1 | Yes | No | Machine room walls have fire/smoke penetrations that shall be filled with appropriate fire caulking. | 7/22/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 7/22/2025 |
| A17.1-2016 : Elevators | 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches | 3.29 | Yes | No | Disconnects and controller shall have car numbering. | 7/22/2025 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.7.1.8 | Yes | No | Machine room controller is missing appropriate alteration code plate. | 7/22/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | Yes | No | Pit lighting shall be at least 10fc across pit floor. | 7/22/2025 |
| A17.1-2016 : Elevators | 5.14 - Supply Piping | 3.19.1 | Yes | No | Remove and properly cap previous oil line elbow fitting. | 7/22/2025 |