Inspection
Inspection Details
Equipment ID
11714
11714
Inspection Date
4/10/2019
4/10/2019
Inspection Type
Alteration
Alteration
Inspector Name
David Folkert
David Folkert
Mechanic Name
Bobby Joe Mehrens
Bobby Joe Mehrens
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
Na
Na
External ID
6bd421e0-1bc4-462c-ac92-3f45f709ea18
6bd421e0-1bc4-462c-ac92-3f45f709ea18
Location
Stoney Creek Inn
1201 N WOODBINE RD, SAINT JOSEPH, MO
1201 N WOODBINE RD, SAINT JOSEPH, MO
Owner
Stoney Creek Inn
1201 N WOODBINE RD, SAINT JOSEPH, MO 64506-2466
1201 N WOODBINE RD, SAINT JOSEPH, MO 64506-2466
Billing
Attn: Stoney Creek Inn
1201 N WOODBINE RD, SAINT JOSEPH, MO 64506-2466
1201 N WOODBINE RD, SAINT JOSEPH, MO 64506-2466
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.37 - Pressure Switch | 306.14 | Yes | No | Need to provide pressure switch on control valve. | 4/11/2019 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate. | 6/25/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post firefighter operating instructions next to hall fire keyswitch | 11/8/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Momentarily pushing car door open button causes doors to fully open while elevator is on firefighter operation phase 2. 14 days to repair before red tag. | 6/25/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 1/5/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Post firefighter instructions next to hall fire service keyswitch | 11/8/2021 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Test and log firefighter operation monthly | 11/8/2021 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | Car door restrictor does not function | 1/5/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate. Phone needs to be reprogrammed | 6/15/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | PHONE DOES NOT RING OUT | 8/16/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | non elev materials being stored in machroom | 9/23/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit floor covered in oil | 9/23/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | smoke head in mach room not working | 8/21/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | Smoke head in mach room not working | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Phase II not working |