Inspection
Inspection Details
Equipment ID
19223
19223
Inspection Date
4/11/2018
4/11/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
Location
Du Pont
4300 Duncan Ave, St. Louis, MO
Phone: (314) 659-3456
4300 Duncan Ave, St. Louis, MO
Phone: (314) 659-3456
Owner
Du Pont
4300 Duncan Ave, St. Louis, MO 63110
4300 Duncan Ave, St. Louis, MO 63110
Billing
Attn: Du Pont
4300 Duncan Ave, , MO 63110
4300 Duncan Ave, , MO 63110
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | x | Phone in elevator does not work. Repair. | 8/6/2018 | |
| conversion | conversion | n/a | Place state operating certificate in machine room. | 3/4/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | OSV not tagged or sealed. Perform OSV test on or before next annual inspection. | 1/24/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1 Illumination and Outlets Required | There are 6 interior cab lights either missing or burnt out. Replace or repair cab lights | 1/24/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. Phone dials out but then gives a busy tone | 1/26/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. Phone dials out but then gives a busy tone | 12/21/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. | 7/15/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/24/2026 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Elevator failed to operate on the emergency generator. Take corrective action and re-test. | 12/13/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/24/2026 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Elevator failed to operate on the emergency generator. Take corrective action and re-test. (2nd Notice) | 2/24/2026 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Elevator failed to operate on emergency power. Take corrective action. |