Inspection
Inspection Details
Equipment ID
20963
20963
Inspection Date
1/26/2018
1/26/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
Location
Clayton High School
#1 Mark Twain Circle, Clayton, MO
Phone: (314) 943-0094
#1 Mark Twain Circle, Clayton, MO
Phone: (314) 943-0094
Owner
School District of Clayton
#2 Mark Twain Circle, Clayton, MO 63105
#2 Mark Twain Circle, Clayton, MO 63105
Billing
Attn: School District of Clayton
#2 Mark Twain Circle, , MO 63105
#2 Mark Twain Circle, , MO 63105
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Static control (brake release) shall be installed. | 11/20/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display the current state operating certificate in the elevator machine room. | 1/28/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | A current tested ABC type fire extinguisher shall be provided in the elevator machine room. | 10/21/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/27/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.3 | Yes | No | Provide means to release brake from outside hoistway. | 8/1/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | Yes | No | Provide means to release brake from outside the hoistway. | 7/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Safety retainers missing on hoistway doors (fire tabs). | 7/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | Yes | No | A means of picking the brake from outside the hoistway must be provided. (2nd Notice) | 10/3/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Category 5 testing is incomplete. Elevator broke down during test. Safeties need to be set with a full load and 125% brake test must be performed. | 10/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | Yes | No | A means of picking the brake from outside the hoistway must be provided. (3rd Notice) |