Inspection
Inspection Details
Equipment ID
7662
7662
Inspection Date
4/15/2019
4/15/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
c8d143ac-3d52-45a4-a8b9-7ae895d445e4
c8d143ac-3d52-45a4-a8b9-7ae895d445e4
Location
Fox Theater
527 N GRAND BLVD, SAINT LOUIS, MO
527 N GRAND BLVD, SAINT LOUIS, MO
Owner
Fox Associates
527 N GRAND BLVD, SAINT LOUIS, MO 63103-1006
527 N GRAND BLVD, SAINT LOUIS, MO 63103-1006
Billing
Attn: Fox Associates
527 N GRAND BLVD, SAINT LOUIS, MO 63103-1006
527 N GRAND BLVD, SAINT LOUIS, MO 63103-1006
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 Access to Pit | Yes | No | Walk in pit door shall have safety switch installed. | 2/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency lighting shall work. | 2/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Required documentation and MCP shall be kept in equipment room including wiring diagrams, oil log, and fire service log recorded monthly. | 1/14/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | Reinstall covers on rope gripper. | 1/14/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | 1/14/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | UNIT IS RED-TAGGED BECAUSE THE ROPE GRIPPER DID NOT WORK WHEN TESTING THE UNINTENDED MOVEMENT UP. | 5/2/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | Reinstall covers on rope gripper. | 1/14/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | The machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. | 1/14/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self locking. | 1/14/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 Access to Pit | No | No | Walk in pit door shall have safety switch. | 1/14/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel | Yes | No | FEO Phase II, hold does not work. Shall not accept car calls while in HOLD. |