Inspection
Inspection Details
Equipment ID
1642
1642
Inspection Date
5/2/2019
5/2/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Gerald Glynn
Gerald Glynn
Mechanic Name
Terry Wingard
Terry Wingard
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
dbae065b-5818-4a71-8dec-49a956a9b571
dbae065b-5818-4a71-8dec-49a956a9b571
Location
Bass Pro- Outdoor World
1935 S CAMPBELL AVE, SPRINGFIELD, MO
1935 S CAMPBELL AVE, SPRINGFIELD, MO
Owner
Attn: UNK
Johnnie Morris Foundation
600 W SUNSHINE ST, SPRINGFIELD, MO 65807
Phone: (000) 000-0000
Email: rjscott@wondersofwildlife.org
Johnnie Morris Foundation
600 W SUNSHINE ST, SPRINGFIELD, MO 65807
Phone: (000) 000-0000
Email: rjscott@wondersofwildlife.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | needs current cedrtifivate posted in machine room | 12/16/2020 |
| conversion | conversion | n/a | No | No | emergency light needs battery | 12/16/2020 |
| conversion | conversion | conversion - reinspect | Yes | No | door close button not working on phase II | 3/5/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | telephone speaker out no two way conversation | 3/5/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | 1.5 Emergency light not working | 12/16/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | I-1 pit needs to be dry and clean | 12/16/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | needs current certificate posted | 12/16/2020 |
| A17.1-1996 : Elevators | 1.14 - Ventilation | 1001.2(a)(14) | No | No | machine room controllers need covers on at all times, if machine room is to hot steps need to be taken to keep it cool | 12/16/2020 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | emergency light not working | 1/15/2021 |
| A17.1-1996 : Elevators | 2.32 - Control Valve | 1004.2(b)(15) | No | No | leakage in control valve frequent releveling | 12/16/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | No Records | 3/5/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Update certificate | 3/5/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit | 3/5/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | No records | 3/5/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Fireman's recall system to be checked monthly | 3/5/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate in machine room | 2/23/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit floor shall be kept dry and free of water | 2/23/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | remove water from pit and replace all wiring and troughing |