Inspection
Inspection Details
Equipment ID
11520
11520
Inspection Date
5/3/2019
5/3/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Relief Valve Pressure
520
520
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
327b47fe-b6ae-42a2-a681-aa2c9dcb2040
327b47fe-b6ae-42a2-a681-aa2c9dcb2040
Location
LaQuinta Inn
1835 W 76 COUNTRY BLVD, BRANSON, MO
1835 W 76 COUNTRY BLVD, BRANSON, MO
Owner
Attn: Vinnie Patel
Vinnie Patel
1835 W 76 COUNTRY BLVD, BRANSON, MO 65616
Phone: (000) 000-0000
Email: qualityinnbranson@gmail.com
Vinnie Patel
1835 W 76 COUNTRY BLVD, BRANSON, MO 65616
Phone: (000) 000-0000
Email: qualityinnbranson@gmail.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Remove all stored material from the machine room as nothing can be stored in there except elevator equipment. | 8/29/2018 | ||
conversion | conversion | n/a | Remove the standing water from the elevator pit and maintain a dry pit | 8/29/2018 | ||
conversion | conversion | n/a | Remove all the molded & deteroated drywall and replace it back to a 2 hour rated assembly. | 8/29/2018 | ||
conversion | conversion | n/a | Re-anchor the top of the guide rails as the wedge anchors are not there. | 8/29/2018 | ||
conversion | conversion | n/a | Obtain and display a current state operating certificate in the machine room. | 8/29/2018 | ||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Obtain and display a current state operating certificate in the machine room | 8/19/2019 | ||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | Have the fire extinguisher re-certified | 8/19/2019 | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Have the emergency phone repaired as there is no dial tone. | 7/13/2020 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Obtain and display a current state operating certificate in the machine room | 8/3/2020 | ||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | Replace the bad pit light from the high water level. | 8/3/2020 | ||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Have the fire extinguisher re-certified as yours out dated. | 5/29/2019 | ||
A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | Repair the HVAC unit in the machine room. | 1/8/2024 | ||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | x | Repair or replace the smoke detector in the machine room as it will not recall the elevator as it has the wrong relay. | 12/29/2023 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | x | Remove the standing 2 feet of water in the pit. | 8/22/2024 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 102 | x | Replace all the damaged electrical conduit, wiring, fixtures below the lower level floor with NEMA 4 wet location equipment. | 8/22/2024 | |
A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.1 | Replace the traveling cable that has been submerged in the water. | 8/23/2024 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Replace the damaged door detector, it won't allow the door to close until it goes into nudging. | 8/23/2024 |