Inspection
Inspection Details
Equipment ID
7851
7851
Inspection Date
4/24/2019
4/24/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
470
470
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
ac455dbf-1e95-4ca2-8025-336a615a3ee8
ac455dbf-1e95-4ca2-8025-336a615a3ee8
Location
Sigma Chemical-Dekalb Bldg
3500 DEKALB ST, SAINT LOUIS, MO
3500 DEKALB ST, SAINT LOUIS, MO
Owner
Sigma Chemical
PO BOX 14508, SAINT LOUIS, MO 63178-4508
PO BOX 14508, SAINT LOUIS, MO 63178-4508
Billing
Attn: Sigma Chemical
3300 S 2ND ST, SAINT LOUIS, MO 63118-3306
3300 S 2ND ST, SAINT LOUIS, MO 63118-3306
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace seal between head and cylinder flanges. Seal leaks during pressure relief test | 4/24/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Cab fire service light on when car not on recall. Conversly, light extingushes when car is on recall need reapair | 4/24/2019 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)1 | No | No | Replace seal between head cylinder flanges. Seal leaks during pressure relief test. | 7/5/2023 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Cab fire service light inoperative on recall. Repair | 12/5/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate. | 7/5/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)5 | No | No | Left side lower panel door guide shoe is broken. Repair | 7/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell and light are inoperative. Repair. | 12/5/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Cab fire service inoperative on recall, repair. Reinspect by 1/5/2020 | 2/27/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Cab fireman's jewel visual signal inoperative. Repair within 30 days. | 6/9/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | 8.6.5.16.5 OSV NOT SEALED TEST DUE IN 2021 | 7/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each elevator | 5/22/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current copy of the state operating certificate shall be displayed in the elevator machine room | 5/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency alarm in car shall be made operable. Re-inspection required | 5/20/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | OSV is not sealed. Noted in last inspection. Perform required testing, seal & tag within 90 days. Re-inspection required | 5/20/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each elevator | 7/5/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 7/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency alarm in car is not working, may need battery replaced. Re-inspection required | 9/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP. | 7/5/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit. | 5/24/2023 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)1 | No | No | Remove mounted fire extinguisher from inside the elevator. See ‘96 204.3a | 5/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 (Re-Inspection) | Yes | No | The sprinkler head in the elevator machine space is required to have a heat detector to activate the shunt trip disconnect before the application of water. Heat detectors shall be installed within 2’ of each sprinkler head to activate the shunt trip disconnect. | 10/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | At least two light fixtures are required for proper illumination inside the elevator cab, only one light fixture was in operation on the day of inspection. Repair fixture. | 10/24/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Firefighters Phase 2 operation shall be tested. | 2/25/2025 |