Inspection
Inspection Details
Equipment ID
12259
12259
Inspection Date
2/9/2018
2/9/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
Location
York House on Lindell
4931 Lindell Blvd, St. Louis, MO
Phone: (314) 345-1090
4931 Lindell Blvd, St. Louis, MO
Phone: (314) 345-1090
Owner
Koplar Properties
50 Maryland Plaza, Ste. 300, St Louis, MO 63108
50 Maryland Plaza, Ste. 300, St Louis, MO 63108
Billing
Attn: Koplar Properties
50 Maryland Plaza, Ste. 300, , MO 63108
50 Maryland Plaza, Ste. 300, , MO 63108
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | conversion - reinspect | x | Fire service, call cancel does not work. | 6/11/2018 | |
conversion | conversion | conversion - reinspect | x | Fire service, hold feature does not work. | 6/11/2018 | |
conversion | conversion | conversion - reinspect | x | Car door restrictor shall work. | 6/11/2018 | |
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | x | x | Phase 2 fire service car call cancel is not operational and shall be repaired and tested. | 5/1/2019 |
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | x | The call cancel feature does not work on Phase 2 fire service and shall be repaired for proper operation. | 6/15/2020 | |
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | x | x | The phase 1 key switch does not work consistently. Repair or replace for proper operation. - Violation corrected 7/7/2020 | 6/15/2020 |
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | x | x | The phase 1 key switch does not work consistently. Repair or replace for proper operation. - Violation corrected 7/7/2020 | 7/7/2020 |
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/22/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | This elevator previously had the ability to operate on standby/emergency power. The generator has now been disconnected but may be re-connected at some point. So long as the elevator does not operate on standby/emergency power, the emergency power fixture at the egress floor for this car shall be removed or covered. If/when the elevators are re-connected to the emergency generator, the emergency power indicator jewel shall be re-installed and standby/emergency power operation of the elevators shall be tested. | 4/22/2021 | ||
A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 205.11 | x | x | Governor safety rope pull out exceeds 42" maximum allowable (60" is the pull out). Verify safety rope is made of corrosion resistant/non-magnetic metal (bronze, brass, etc). Appears to be steel rope and is magnetic. Must be repaired and reinspection required before returning to service. Elevator RED TAGGED. | 5/23/2024 |
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | x | Phase 1 fire hat does not remain illuminated while on fire service. | 5/23/2024 | |
A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | x | Car door restrictor shall work at all floors. | 5/23/2024 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | x | Phase 1 fire hat does not remain illuminated while on fire service. (Violation remains after 5/23/24 re-inspection) | ||
A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | x | Car door restrictor shall work at all floors. (Violation remains after 5/23/24 re-inspection) |