Inspection
Inspection Details
Equipment ID
6612
6612
Inspection Date
4/24/2019
4/24/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Kevin Liles
Kevin Liles
Relief Valve Pressure
340
340
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
83b5866a-1bd1-4439-a0e7-b11bf0d33e5c
83b5866a-1bd1-4439-a0e7-b11bf0d33e5c
Location
Boeing- Bldg 598
2600 N HIGHWAY 94, SAINT CHARLES, MO
2600 N HIGHWAY 94, SAINT CHARLES, MO
Owner
Boeing Co
PO BOX 516, SAINT LOUIS, MO 63166-0516
PO BOX 516, SAINT LOUIS, MO 63166-0516
Billing
Attn: Boeing Co
PO BOX 516, SAINT LOUIS, MO 63166-0516
PO BOX 516, SAINT LOUIS, MO 63166-0516
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | Need a maintenance control program on site | 10/22/2025 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | Yes | No | Overspeed valve testing is past due. Tessting to be completed in 30 days are less otherwise unit will be red tagged out of service | 7/10/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service call cancel button shall work. 14 days to be corrected and re-inspected or unit to be red tagged. | 10/22/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | Yes | No | Fire service phase 2 key switch shall have only 2 positions. Unit does not have "HOLD". Bezel is correct with only "OFF" and "ON". | 10/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 10/22/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | This repair/alteration inspection included witnessing working pressure and relief pressure. The working pressure was 340#. While testing for relief pressure, the unit went down. This inspection was not completed. Relief valve pressure shall be successfully tested. | 2/26/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service call cancel button shall work. 14 days to be corrected and re-inspected or unit to be red tagged. Violation unable to be checked at time of alteration inspection on 10/16/25 due to unit going down. | 2/26/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | Yes | No | Fire service phase 2 key switch shall have only 2 positions. Unit does not have "HOLD". Bezel is correct with only "OFF" and "ON". Violation unable to be checked at time of alteration inspection on 10/16/25 due to unit going down. | 2/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Yes | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 2/26/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service call cancel button shall work. | |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | No | No | Fire service phase 2 key switch shall have only 2 positions. Unit does not have "HOLD". Bezel is correct with only "OFF" and "ON". |