Inspection
Inspection Details
Equipment ID
17061
17061
Inspection Date
6/20/2018
6/20/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Relief Valve Pressure
600
600
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
18/17
18/17
External ID
17061
17061
Location
Target- St. Louis
4255 Hampton Ave, St. Louis, MO
Phone: (314) 802-0122
4255 Hampton Ave, St. Louis, MO
Phone: (314) 802-0122
Owner
Target Corporation-Target Store T1515
PO Box 111, Minneapolis, MN 55440
PO Box 111, Minneapolis, MN 55440
Billing
Attn: Target Corporation-Target Store T1515
PO Box 111, , MN 55440-0111
PO Box 111, , MN 55440-0111
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post Mo State operating permit in machine room | 10/19/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Need testing procedures in MCP on or before 1/1/22 | 5/22/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room Overspeed valve set at 171 | 2/10/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | Front and rear restrictors shall work. | 7/3/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | Machine room fire extinguisher shall be permanently mounted to the wall. | 7/3/2025 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | Yes | No | Lighting disconnect fused improperly. Replace 20A fuse with proper 15A. | 7/3/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | Hall calls shall work. | 7/3/2025 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | Yes | No | Adjust upthrusts for proper clearances (2nd floor front). | 7/3/2025 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | Yes | No | Adjust upthrusts for proper lower gap opening. | 7/3/2025 |
| A17.1-2016 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | Yes | No | Adjust hoistway access limit (PIT) for proper stopping heights. | 7/3/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | INCOMPLETE: Remaining testing needed is as follows: pump pressures and speed, relief pressure, OSV, rear door torque, phase I & II fire service, FAID and recalls, battery lowering, COP stop, low oil, and 15 min static testing. | 7/3/2025 |