Inspection
Inspection Details
Equipment ID
1334
1334
Inspection Date
5/7/2019
5/7/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
e277e0aa-0bc5-4156-b694-af42c9a06b96
e277e0aa-0bc5-4156-b694-af42c9a06b96
Location
Plato's Cave
3524 KEETER ST, BRANSON, MO
3524 KEETER ST, BRANSON, MO
Owner
REPVBLIK-Branson
3524 KEETER ST, BRANSON, MO 65616-3578
3524 KEETER ST, BRANSON, MO 65616-3578
Billing
Attn: Plato's Cave
3524 KEETER ST, BRANSON, MO 65616-3578
3524 KEETER ST, BRANSON, MO 65616-3578
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Dispaly a current state operating certificate in the machine room. | 10/23/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone as the incomming line is dead | 7/2/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Repair the emergency phone as the incoming line is dead it has no dial tone. | 7/6/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room. | 7/1/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Remove all the added phone/ wifi wiring from the elevator machine room. | 7/1/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Repair or replace the emergency phone as there is no dial tone. | 11/22/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | No | No | Provide lockable disconnect switchs for the car lights in the machine room | 7/1/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Replace the missing smoke detector at the top of the hoistway | 11/22/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 6/6/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone as the incoming line has no dial tone. |