Inspection
Inspection Details
Equipment ID
19423
19423
Inspection Date
4/12/2019
4/12/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
230
230
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
a7f85e4c-af01-4050-a3bd-deaa017d1c6b
a7f85e4c-af01-4050-a3bd-deaa017d1c6b
Location
Kimberley Bldg
2510 S BRENTWOOD BLVD, BRENTWOOD, MO
2510 S BRENTWOOD BLVD, BRENTWOOD, MO
Owner
The Frank Company
2510 S BRENTWOOD BLVD, BRENTWOOD, MO 63144-2328
2510 S BRENTWOOD BLVD, BRENTWOOD, MO 63144-2328
Billing
Attn: The Frank Company
2510 S BRENTWOOD BLVD, SAINT LOUIS, MO 63144-2328
2510 S BRENTWOOD BLVD, SAINT LOUIS, MO 63144-2328
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/10/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 4/10/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | 4/10/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 4/10/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Where other existing machines and equipment essential to the operation and purpose of the building are located in the machine room or space, the elevator related equipment and machines shall be separated by a substantial grill constructed of noncombustible material not less than six feet (6') high and the grill shall be of a design that will reject a ball two inches (2") in diameter. All rooms or enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. | 4/10/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Hoistways containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction to its full height. There are numerous holes in the hoistway. | 4/10/2026 |
| A17.1-2016 : Elevators | 3.2 - Car top light and outlet | 8.11.3.1.3(b) | No | No | Light fixture on top of the car is broken. | 4/10/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 4/10/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self-closing and self-locking and operable from the interior space without the use of a key. | 4/10/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/10/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Replace missing upthrust roller bearings on hoistway doors (3rd and 4th landings). | 4/10/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self-closing and self-locking . No closer on door and door does not properly fit door frame. REPEAT VIOLATION. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Non-elevator related items shall not be stored in Machine Room. REPEAT VIOLATION. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Where other existing machines and equipment essential to the operation and purpose of the building are located in the machine room or space, the elevator related equipment and machines shall be separated by a substantial grill constructed of noncombustible material not less than six feet (6') high and the grill shall be of a design that will reject a ball two inches (2") in diameter. All rooms or enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key.REPEAT VIOLATION. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine Room shall have proper Fire Extinguisher and shall have current. |