Inspection
Inspection Details
Equipment ID
18471
18471
Inspection Date
4/12/2019
4/12/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
e5d4e70b-c8cb-4926-b6e0-4cfa6a944637
e5d4e70b-c8cb-4926-b6e0-4cfa6a944637
Location
City Place 5
845 N NEW BALLAS CT, CREVE COEUR, MO
845 N NEW BALLAS CT, CREVE COEUR, MO
Owner
Attn: City Place 5
City Place 5
845 N New Ballas Court, Creve Coeur, MO 63141
Phone: (000) 000-0000
City Place 5
845 N New Ballas Court, Creve Coeur, MO 63141
Phone: (000) 000-0000
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | This elevator is equipped with an over speed valve. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 6/1/2021 | ||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/1/2022 | ||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/26/2022 | ||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/24/2024 | ||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | x | Fire service phase II switch key shall not be removable in "ON" position. | ||
A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.2 | x | Machine room oil coolers are wired to cab lighting circuit. Shall be dedicated circuits. | ||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and related on-site documentation shall be provided in the machine room. Missing PM/repair/callback/testing logs for 2023, 2024 and 2025. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Adjust upthrust roller bearings for proper clearance to door hanger track (1st Floor). | |||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)9 Capacity Plate | Replace unreadable in-car capacity plate/unit number plate. | |||
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | Fire service testing must be documented monthly. |