Inspection
Inspection Details
Equipment ID
12184
12184
Inspection Date
5/1/2019
5/1/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Charles Brinkman
Charles Brinkman
Mechanic Name
Perry Nolker
Perry Nolker
Relief Valve Pressure
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
85114ed2-0a22-4c80-9ba7-3bc8ce43ddf6
85114ed2-0a22-4c80-9ba7-3bc8ce43ddf6
Location
The Gallery Apartments
3450 RUSSELL BLVD, SAINT LOUIS, MO
3450 RUSSELL BLVD, SAINT LOUIS, MO
Owner
Brandonview LLC
4140 WASHINGTON BLVD, SAINT LOUIS, MO 63108-3148
4140 WASHINGTON BLVD, SAINT LOUIS, MO 63108-3148
Billing
Attn: Brandonview LLC
Brian Hayden
4140 WASHINGTON BLVD, SAINT LOUIS, MO 63108-3148
Brian Hayden
4140 WASHINGTON BLVD, SAINT LOUIS, MO 63108-3148
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | 1) Where spring buffers are used, the bottom runby shall be not less than 6 in. The counterweight runby is only 5 in. suspension cables need to be shortened. | 5/1/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | 2) Installation of electrical equipment and wiring shall conform to NFPA 70. The Flexable Metal Conduit to fan and switch to emergency exit has been pulled from box connector or box connector broken exposing wires. | 11/19/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 1) The emergency alarm bell is not functioning properly, can barely be heard not meeting the requirement of not less than 80 dBA nor greater than 90 dBA at 3 m (10 ft). | 7/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 | Yes | No | 2) The two-way communication device in the machine room doesn't provide communication to the elevator car. Ref: 2.27.1.1.4 | 7/10/2020 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(f) | No | No | 1. The duplex receptacle that has been provided in the machine room is not operable. | 1/13/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | 2. A record that shall include the maintenance tasks listed with the associated requirements of Section 8.6 identified in the Maintenance Control Program (8.6.1.2.1), other tests (see 8.6.1.2.2), examinations and adjustments, and the specified scheduled intervals shall be maintained. | 1/13/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.2 Callbacks (Trouble Calls) Documentation | No | No | 3. A record of callbacks shall be maintained and shall include the description of reported trouble, dates, time, and corrective action(s) taken that are reported by any means to elevator personnel. | 1/13/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | 4. All elevators provided with Firefighters’ Emergency Operation shall be subjected monthly, by authorized personnel, to Phase I recall by use of the key switch. Ref: 8.6.10.1 | 1/13/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone is not working. | 5/24/2023 |