Inspection
Inspection Details
Equipment ID
17549
17549
Inspection Date
4/29/2019
4/29/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
18
18
External ID
1fbc599a-058c-482e-a627-1847bc9dd518
1fbc599a-058c-482e-a627-1847bc9dd518
Location
The Chase Park Plaza
212 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO
212 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO
Owner
Chase Park Plaza Hotel
212 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO 63108-1266
212 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO 63108-1266
Billing
Attn: Chase Park Plaza
212 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO 63108-1266
212 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO 63108-1266
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | Machine room door will not open/close without prying. Will not lock either Need to be self-closing. | 3/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | Barricade exterior machine room doors which swing out to top level parking garage that present fall hazard from upper deck. | 3/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Water in pit. Needs to be kept clean and dry. | 3/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Fire extinguisher in the elevator machine room is expired. Update fire extinguisher | 3/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The elevator pit is full of water and must have a working sump pump to keep the pit dry | 3/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted:The audible and visual signal device did not sound/light when phase I was activated. | 5/20/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | A machine room lighting fixture was not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | 3/31/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The weight test shall be performed and the safeties set before the inspection is completed. | 5/20/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted:The audible and visual signal device did not sound/light when phase I was activated. Repair and reinspection required within 14 days. | 5/22/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | A machine room lighting fixture was not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | 3/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | A machine room lighting fixture was not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | 4/3/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.28 - Counterweight and counterweight buffer | 2.21 | No | No | There is a bottom guide roller on the counterweight that is cracked and shall be replaced | 4/3/2026 |