Inspection
Inspection Details
Equipment ID
17548
17548
Inspection Date
4/26/2019
4/26/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
430
430
Slide
Governor Rope Pull
Door Closing Force
27
27
External ID
e4b38450-3e0e-47a1-b23e-7236352128cd
e4b38450-3e0e-47a1-b23e-7236352128cd
Location
Chase Park Plaza Hotel
212 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO
212 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO
Owner
Chase Park Plaza Hotel
212 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO 63108-1266
212 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO 63108-1266
Billing
Attn: Chase Park Plaza
212 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO 63108-1266
212 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO 63108-1266
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Stop switch needs to be overridden on Phase 1 | 3/31/2026 |
| conversion | conversion | n/a | No | No | Emergency light not working | 3/31/2026 |
| conversion | conversion | n/a | No | No | The heat detector needs to be 2 ft or less from sprinkler heads | 3/31/2026 |
| conversion | conversion | n/a | No | No | Seal all penetrations in the hostway | 3/31/2026 |
| conversion | conversion | n/a | No | No | Pit needs to be clean and dry. Remove oil and debris | 3/31/2026 |
| conversion | conversion | n/a | No | No | Sprinklers in hoistway at top. Need smoke detector and heat detectors at top of hoistway | 3/31/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | Top floor door closer on hoistway door is broken. | 3/31/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit is covered in oil. Clean | 3/31/2026 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | In car stop switch is not overridden on Phase I Fire Service when car is in flight. | 3/19/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean oil soaked pit pads. | 3/31/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Overspeed valve is not sealed. Perform OSV test on or before next annual inspection. | 3/31/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Car stop switch not overridden on Phase I | 4/14/2022 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Install heat and smoke detectors at top of hoistway and less than 2 ft from sprinkler head in machine room and pit. Did not red tag. | 4/14/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Repair hoistway penetrations in machine room around piping. | 3/31/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit. | 3/31/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 1. Replace broken limit switch roller at top hoistway. Rule G-1, Missouri minimum. Rule 8.11.3.1.3(F) A17.1, 2016. Rule 3.6, A17.2, 2014. | 3/31/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | 2. Overspeed valve is not sealed and needs full load test and tripping speed checked. Rule 8.6.5.16.5, A17.1, 2016.Reinspect by 7-14-22(90 days) | 4/14/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | Repair top floor hoistway door closer. Missing Hardware | 3/31/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing roller on top directional switch | 3/31/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace damaged roller on car top slow down switch | 3/31/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean oil soaked pads from elevator pit | 3/31/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | In car stop switch shall be overridden on phase 1 fire service. Rule s-1 this violation has been written up multiple times. Repair and reinspect by 5-14-23 (30 days) or elevator wil be red tagged and removed from service | 9/18/2024 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Elevators hoistway shall be fully enclosed to their full height | 3/31/2026 |