Inspection
Inspection Details
Equipment ID
2682
2682
Inspection Date
5/8/2019
5/8/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Dennis Drinkard
Dennis Drinkard
Mechanic Name
James Reischman
James Reischman
Relief Valve Pressure
Slide
16"
16"
Governor Rope Pull
300
300
Door Closing Force
20/18
20/18
External ID
36c4e549-3b8f-4c91-a1d5-02d4a89961ae
36c4e549-3b8f-4c91-a1d5-02d4a89961ae
Location
Flarsheim Hall
5110 ROCKHILL RD, KANSAS CITY, MO
5110 ROCKHILL RD, KANSAS CITY, MO
Owner
Attn: UMKC- Parking Structure
UMKC- Parking Structure
1011 E 51ST ST, KANSAS CITY, MO 64110
Phone: (000) 000-0000
Email: hickmanch@umkc.edu
UMKC- Parking Structure
1011 E 51ST ST, KANSAS CITY, MO 64110
Phone: (000) 000-0000
Email: hickmanch@umkc.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | repair both the front and rear car door restrictors neither are working | 10/25/2019 |
| conversion | conversion | n/a | No | No | fire extinguisher is to be inspected and tagged annually, tag is from 2015 | 10/25/2019 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | perform monthly fire service test and post log in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | machine room fire extinguisher needs to be recharged, the gauge is on zero it has been discharged, inspection tag is from 2015 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. The one in the machine room is from 2015. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | both the front and rear door restrictors need to be adjusted so they work | 6/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | could not get the seismic to trip, provide written instruction in the machine room with the seismic testing procedures | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | fire service phase 2 would not close the door to run the elevator, the door was bouncing on the open limit | 6/13/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | the emergency light came on but the alarm bell did not work | 6/13/2023 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | machine room fire extinguisher inspection tag is expired from 2013, have the fire extinguisher inspected and tagged annually | |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | both front and rear door restrictors are not working, adjust and repair door restrictors | 6/4/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | fire service phase 1 keyswitch collar markings can no longer be read, replace keyswitch collar (2.27.3.1.1(b)) [non red tag] | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine room fire extinguisher inspection tag is from 2013, have the fire extinguisher inspected and tagged annually | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Fire service phase 1 keyswitch collar markings can no longer be read, replace collar | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | Both front and rear door close force needs to be adjusted so that the pressure is less than 30lbs | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Both front and rear door restrictors are not working, repair door restrictors | 8/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lights did not come on, repair it so the emergency lights work | 8/30/2024 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Update expired fire extinguisher |