Inspection
Inspection Details
Equipment ID
18523
18523
Inspection Date
4/17/2019
4/17/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
18F/20R
18F/20R
External ID
e949d640-2ba6-4bf8-8d3c-42ed0b3c76eb
e949d640-2ba6-4bf8-8d3c-42ed0b3c76eb
Location
First Christian Church- Washington
6890 HIGHWAY 100, WASHINGTON, MO
6890 HIGHWAY 100, WASHINGTON, MO
Owner
First Christian Church- Washington
6890 HIGHWAY 100, WASHINGTON, MO 63090-1121
6890 HIGHWAY 100, WASHINGTON, MO 63090-1121
Billing
Attn: First Christian Church- Washington
6890 HIGHWAY 100, WASHINGTON, MO 63090-1121
6890 HIGHWAY 100, WASHINGTON, MO 63090-1121
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work. | 9/30/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) | Yes | Yes | Phase 2 fire service shall be operational. Elevator left in service and violation shall be corrected in 30 days. | 3/2/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 3/2/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/19/2023 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Unit is equipped with an overspeed valve. A category 5 test is due on the overspeed valve in 2022. | 9/21/2022 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.2 | Yes | No | Heat detectors shall be installed within 24 inches of each sprinkler head located in the elevator machine room and shall active the shunt trip. | 9/21/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | This elevator is equipped with an overspeed valve that in not sealed. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 9/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency bell and emergency light did not work when the 110V disconnect was de-energized. | 9/21/2022 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.2 | Yes | No | Heat detectors shall be installed within 24 inches of each sprinkler head located in the elevator machine room and shall active the shunt trip. | 11/6/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency bell and emergency light did not work when the 110V disconnect was de-energized. | 11/6/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 5/11/2026 |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | No | No | Jack head drain tube shall be routed to measurable containers in pit. Currently tubes are routed straight to pump unit. |