Inspection
Inspection Details
Equipment ID
19451
19451
Inspection Date
4/23/2019
4/23/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Alex Brinkman
Alex Brinkman
Relief Valve Pressure
240
240
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
52281de5-cf49-440e-ba48-168377efe6cb
52281de5-cf49-440e-ba48-168377efe6cb
Location
West End Lofts
4100 FOREST PARK AVE, SAINT LOUIS, MO
4100 FOREST PARK AVE, SAINT LOUIS, MO
Owner
Attn: Danette Dietz
West End Lofts c/o Sentry Management
9666 OLIVE BLVD STE 116, SAINT LOUIS, MO 63132
Phone: (314) 994-7440
Email: ddietz@sentrymgt.com
West End Lofts c/o Sentry Management
9666 OLIVE BLVD STE 116, SAINT LOUIS, MO 63132
Phone: (314) 994-7440
Email: ddietz@sentrymgt.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | In cab emergency telephone shall work. | 6/22/2018 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | The car door restrictor shall be operational. | 7/1/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. (This item is for notification purposes for future violation in 2022) | 6/2/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 9/29/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/29/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/26/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 6/26/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | CAR DOOR RESTRICTOR SHALL WORK AT ALL FLOORS. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire Service must be tested and properly documented monthly on Log Sheet located in the MCP. |