Inspection
Inspection Details
Equipment ID
8535
8535
Inspection Date
5/22/2019
5/22/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Tim Crafton
Tim Crafton
Mechanic Name
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
25a4ffc3-e1c6-41e8-b44f-bda19fcdcf06
25a4ffc3-e1c6-41e8-b44f-bda19fcdcf06
Location
Saint Louis Galleria
1155 SAINT LOUIS GALLERIA, RICHMOND HEIGHTS, MO
1155 SAINT LOUIS GALLERIA, RICHMOND HEIGHTS, MO
Owner
General Growth Properties
1155 SAINT LOUIS GALLERIA, SAINT LOUIS, MO 63117-1159
1155 SAINT LOUIS GALLERIA, SAINT LOUIS, MO 63117-1159
Billing
Attn: General Growth Properties
1155 SAINT LOUIS GALLERIA, SAINT LOUIS, MO 63117-1159
1155 SAINT LOUIS GALLERIA, SAINT LOUIS, MO 63117-1159
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | A17.1 2.27.3.1.6(h )FIREMANS SERVICE ILLUMINATED VISUAL & AUDIBLE SIGNAL IN CAR PANEL NOT WORKING | 2/28/2020 | |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | Repair leakage under tank. Possibly a supply hose clamp to control valve leak. | 12/5/2023 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | OSV is not sealed. Perform OSV test on or before next annual inspection. | 12/5/2023 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | Car door restrictor does not work. | 6/7/2022 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Place current state operating certificate in machine room. | 12/5/2023 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Elevator cab phone does not work on 110v emergency power or normal power. Repair or replace | 6/5/2023 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
| MO Minimum : Elevators | (I) - Pits | (I)1 | The pit shall be kept clean and dry. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | Evacuation procedures are missing from the MCP. | |||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)6 | x | Door safety edge is not working. | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replace any missing/damaged panels, buttons, or spacers on the COP. | |||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Relief valve and fire service shall be tested and completed. |