Inspection
Inspection Details
Equipment ID
8541
8541
Inspection Date
5/22/2019
5/22/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Tim Crafton
Tim Crafton
Mechanic Name
Relief Valve Pressure
370
370
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
3d0cd48e-f779-4c51-a0cb-8da4fef45e50
3d0cd48e-f779-4c51-a0cb-8da4fef45e50
Location
Saint Louis Galleria
1155 SAINT LOUIS GALLERIA, RICHMOND HEIGHTS, MO
1155 SAINT LOUIS GALLERIA, RICHMOND HEIGHTS, MO
Owner
General Growth Properties
1155 SAINT LOUIS GALLERIA, SAINT LOUIS, MO 63117-1159
1155 SAINT LOUIS GALLERIA, SAINT LOUIS, MO 63117-1159
Billing
Attn: General Growth Properties
1155 SAINT LOUIS GALLERIA, SAINT LOUIS, MO 63117-1159
1155 SAINT LOUIS GALLERIA, SAINT LOUIS, MO 63117-1159
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | A17.1 2.27.3.3 Phase II Emergency In-Car Operation. NOT WORKING | 2/19/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Place current state operating certificate in machine room. | 12/5/2023 |
| A17.1-1996 : Elevators | 1.4 - Sills and car floor | 1001.2(a)(4) | No | No | Bottom floor landing sill guard needs to be reattached. | 12/5/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Evacuation procedures are missing from the MCP. | 6/3/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing log is missing from the MCP. | 6/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Door restrictor needs to be adjusted. | 6/3/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. | 6/3/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Phone door is damaged and can not easily be opened. Repair phone door and install a pull handle. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top shall be cleaned | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Door Gib on 2nd Floor shall be replaced | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Door restrictor shall be repaired to prevent doors from opening more than 4" when not at a landing. |