Inspection
Inspection Details
Equipment ID
19395
19395
Inspection Date
5/22/2019
5/22/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Tim Crafton
Tim Crafton
Mechanic Name
Relief Valve Pressure
N/A
N/A
Slide
Governor Rope Pull
Door Closing Force
N/A
N/A
External ID
c9d22b28-b1ea-4faa-aa60-23084da95be0
c9d22b28-b1ea-4faa-aa60-23084da95be0
Location
Best Buy #833
8350 EAGER RD, BRENTWOOD, MO
8350 EAGER RD, BRENTWOOD, MO
Owner
Attn: Best Buy #833
Best Buy #833
PO Box 9450, Minneapolis, MN 55440
Phone: (612) 291-4460
Email: businesslicense@bestbuy.com
Best Buy #833
PO Box 9450, Minneapolis, MN 55440
Phone: (612) 291-4460
Email: businesslicense@bestbuy.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 210.2 | No | No | Replace broken door closer. | 1/5/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. | 5/22/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | A17.1-1996 : Elevators 1.6 - Car emergency signal 1201.2(a)(6) Phone in elevator cab does not work. | 11/25/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. | 12/23/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written maintenance control program shall be provide for each elevator on site. | 1/5/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.2 Collection of Oil Leakage | No | No | Scavenger pumps that do not record amount of oil to be returned to the tank cannot be installed in the elevator pit. | 1/5/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency light does not work on 110v emergency power | 12/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | There is a scavenger pump in the pit that must be replaced with a 5 gallon bucket in order to record oil leakage | 6/30/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each elevator | 1/27/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/27/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Access to machine room shall be kept clear & unobstructed | 1/27/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 1/27/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Unit has oil scavenger pump in pit. Remove pump and replace with proper container so oil leakage from cylinder can be measured | 1/27/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in the cab does not work. Reinspection required in 14 days | 1/16/2025 |