Inspection
Inspection Details
Equipment ID
15926
15926
Inspection Date
6/15/2017
6/15/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
32
32
External ID
Location
Westwood Nursing Center
1801 N Gaines, Clinton, MO
Phone: (660) 885-8196
1801 N Gaines, Clinton, MO
Phone: (660) 885-8196
Owner
Golden Living Center
1000 Fianna Way, Fort Smith, AR 72919
1000 Fianna Way, Fort Smith, AR 72919
Billing
Attn: Golden Living Center
1000 Fianna Way, , AR 72919
1000 Fianna Way, , AR 72919
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | ledge on wall of hoistway oposite of the car opening has a ledge that is greater than 4 inches and needs to be beveled | 3/2/2023 | ||
| conversion | conversion | n/a | clean oil spilled on the machine room floor | 3/2/2023 | ||
| conversion | conversion | n/a | adjust door close force to below 30 lbs, measured 32 | 3/2/2023 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean the pit of standing hydraulic oil. | 2/18/2023 | ||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Provide a lamp for the pit light. | 2/18/2023 | ||
| MO Minimum : Elevators | (I) - Pits | (I)8 | Replace the cover for the sump hole. | 2/18/2023 | ||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | replace missing light bulb in pit light | 2/18/2023 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | water in pit, sump hole is full, sump is not running | 2/18/2023 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | the 6 inch ledge at the back of the hoistway at the top landing floor should be beveled | 2/18/2023 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | x | I (1) Water in the Elevator Pit sump pump quite working Replace the sump pump. | 2/14/2023 | |
| MO Minimum : Elevators | (I) - Pits | (I)5 | Existing Pit Ladder needs replaced. Pit depth is 47.5 inches deep with the existing ladder hand holds of 24 inches above access landing sill, Which presents a safety hazard to enter pit for maintenance service. | 5/31/2023 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | In case of fire don't use elevator signage needed | 7/8/2024 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Machine room door must be self-locking | 7/8/2024 |