Inspection
Inspection Details
Equipment ID
24504
24504
Inspection Date
5/13/2019
5/13/2019
Inspection Type
New Installation
New Installation
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Steven Perez
Steven Perez
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
4af7dc79-5ff5-4c25-8f4c-de16ff1efb28
4af7dc79-5ff5-4c25-8f4c-de16ff1efb28
Location
Ameristar Casinos St. Charles
One Ameristar Blvd, Saint Charles, MO
Phone: (314) 705-7907
Email: dfdriscoll@paric.com
One Ameristar Blvd, Saint Charles, MO
Phone: (314) 705-7907
Email: dfdriscoll@paric.com
Owner
Attn: David Driscoll
Pinnacle Entertainment
8918 Spanish Ridge Ave, Las Vegas, NV 89148
Phone: (314) 705-7907
Email: dfdriscoll@paric.com
Pinnacle Entertainment
8918 Spanish Ridge Ave, Las Vegas, NV 89148
Phone: (314) 705-7907
Email: dfdriscoll@paric.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.1 - General fire protection | 6.1.1 | Yes | No | All construction around escalator shall be completed. | 8/6/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.4 - Entrance and egress ends | 6.1.3.6 | Yes | No | Finish upper landing floor. | 8/6/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.5 - Lighting | 6.1.7.2 | Yes | No | Lighting at lower deck plate may be below 5 ft candles at night. | 8/6/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.14 - Code data plate | 8.9 | No | No | Post installation code data tag on unit. | 11/3/2020 |
| A17.1-2016 : Elevators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.15.19 | Yes | No | Provide skirt index test, record results. | 9/15/2023 |
| A17.1-2016 : Elevators | 7.7 - Combplate and comb step impact device | 8.6.8.15.18 | Yes | No | Provide comb impact test, adjust as needed. | 9/15/2023 |
| A17.1-2016 : Elevators | 7.3 - Handrails | 8.6.8.15.13 | No | No | Observed crack on right side hand rail, replace. | 8/9/2023 |
| A17.1-2016 : Elevators | 8.4 - Drive machine and brake | 8.6.8.15.4 | Yes | No | Provide torque testing of unit brake. | 9/15/2023 |
| A17.1-2016 : Elevators | 8.12 - Steps, step chains, and trusses | 8.6.8.13 | No | No | Provide unit clean down. | 8/9/2023 |
| A17.1-2016 : Elevators | 7.19 - Maintenance records | 8.6.1.2.1(a) | No | No | Provide MCP. | 8/9/2023 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 8/9/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3 Step/Skirt Performance Index | Yes | No | Need index print out to complete inspection. Re-inspection required | 3/13/2024 |