Inspection
Inspection Details
Equipment ID
9807
9807
Inspection Date
5/10/2019
5/10/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
28
28
External ID
a9f369a6-6f1b-48f9-9a58-17d0ce95ba67
a9f369a6-6f1b-48f9-9a58-17d0ce95ba67
Location
Edward Jones Dome
901 N BROADWAY, SAINT LOUIS, MO
901 N BROADWAY, SAINT LOUIS, MO
Owner
Attn: America's Center
America's Center
701 CONVENTION PLZ, SAINT LOUIS, MO 63101
Phone: (314) 342-5118
Email: accountspayable@explorestlouis.com
America's Center
701 CONVENTION PLZ, SAINT LOUIS, MO 63101
Phone: (314) 342-5118
Email: accountspayable@explorestlouis.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Elevator machine room cannot be used for storage of non-elevator equipment. | 4/9/2026 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Full load car safety test failed due to governor jaw malfunction. Repair governor jaws and retest pull through force and perform car safety test with full load. Elevator red-tagged until repair is made and reinspected. | 2/5/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Written maintenance control program shall be provided on-site. | 4/9/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Elevator machine room cannot be used for storage. | 4/9/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light & bell are not working. Re-inspection required | 4/9/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self closing and self locking | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Elevator machine room cannot be used for storage of non-elevator equipment. Remove all non elevator related materials from machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MCP is not filled out, including monthly fire service checks | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace deteriorated bushings on cartop hoist rope shackle hitch | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired, have serviced or replaced | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace all missing braille plates on hoistway door jambs as needed |