Inspection
Inspection Details
Equipment ID
13727
13727
Inspection Date
2/21/2018
2/21/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
AT & T - One Bell Center
1010 Pine St, St. Louis, MO
Phone: (314) 235-9992
1010 Pine St, St. Louis, MO
Phone: (314) 235-9992
Owner
AT&T-St. Louis
12851 Manchester, Room 1-W-10, Des Peres, MO 63131
12851 Manchester, Room 1-W-10, Des Peres, MO 63131
Billing
Attn: AT&T- Elevator Management c/o Lerch Bates
4201 Northview Dr Suite 314, , MD 20716
4201 Northview Dr Suite 314, , MD 20716
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | conversion - reinspect | x | Provide Emergency Phone | 3/29/2019 | |
A17.1-1996 : Elevators | 4.4 - Hoistway door locking devices | 111 | x | Interlock cover on the 17th floor missing. | 7/27/2020 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone shall work. | 7/27/2020 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 2/24/2021 | |
A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | Replace missing door close button tactile plate in car operating panel. | |||
A17.1-1996 : Elevators | 3.20 - Governor rope | 1001.2(c)(26) | x | x | Overspeed governor rope tension sheave is bottomed out. Shorten governor rope. Red tagged. | 2/24/2021 |
A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | Replace missing door close button tactile plate in car operating panel. | |||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 9/2/2022 | |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Replace missing tactile plate on COP | |||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Replace CO2 fire extinguishers with ABC type. Both elevator machine room and secondary spaces. | |||
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | Provide existing emergency lights and bell to work. | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replace missing pull straps (3), floors 2B,S,1.. hoistway doors. | |||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | x | Provide testing of the elevator on emergency power. | ||
A17.1-1996 : Elevators | 4.12 - Standby power selection switch | 1001.2(d)(12) | x | Provide testing of the elevator emergency power selector switch (fire command room). |