Inspection
Inspection Details
Equipment ID
19829
19829
Inspection Date
5/7/2019
5/7/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Aaron Bagley
Aaron Bagley
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
8038e536-6b68-40a3-8e3e-f4a516384b27
8038e536-6b68-40a3-8e3e-f4a516384b27
Location
The Kingsbury
501 CLARA AVE, SAINT LOUIS, MO
501 CLARA AVE, SAINT LOUIS, MO
Owner
Mac Property Management
32 N DEAN ST # 2, ENGLEWOOD, NJ 00000
32 N DEAN ST # 2, ENGLEWOOD, NJ 00000
Billing
Attn: Kingsbury STL LLC c/o Mac Properties
18 S KINGSHIGHWAY BLVD, SAINT LOUIS, MO 63108-1356
18 S KINGSHIGHWAY BLVD, SAINT LOUIS, MO 63108-1356
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Need access to overhead machine space (from roof deck to access door is over 4" no ladder or steps) | 12/2/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | FEO Phase II shall work | 4/25/2019 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Governor rope fails to meet requirements and needs to be replaced. | 5/7/2019 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are stretched and need to be re-socketed on the basement drum machine. | 5/7/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)4 | No | No | Hoistway doors have gaps where someone could put their hand through while car is running. | 3/10/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)4 | No | No | Car gate has gaps where someone could put their hand in while car is running. Unsafe | 3/10/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | No | No | Hoistway containing passenger elevators shall be fully enclosed and the enclosure shall be of solid construction to its full height. | 3/10/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | No | No | All means of access to elevator machine room shall be of a permanent nature and shall be constructed and maintained in a clear and unobstructed manner. Overhead access shall not be by a step ladder. | 3/10/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.3 - Firefighters' service (A17.1-1984 through A17.1a-1988 and A17.3) | 8.11.2.1.4(l) | Yes | Yes | Elevators with fire service shall comply with the edition of ASME A17.1 that was constructed to City mandated fire service in 1993. Repair inoperative Phase II fire recall. Phase II did not work at all but it did return on Phase I. 30 days to repair and reinspect. | 3/10/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.9 - Guarding of exposed auxiliary equipment | 8.11.2.1.2(i) | No | No | Repair wire enclosure guarding secondary area. | 3/10/2021 |