Inspection
Inspection Details
Equipment ID
15296
15296
Inspection Date
5/9/2019
5/9/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
e8cc54c4-3448-4a08-b649-474f5e14d642
e8cc54c4-3448-4a08-b649-474f5e14d642
Location
Staybridge Inn & Suites
1155 TECHNOLOGY DR, O FALLON, MO
1155 TECHNOLOGY DR, O FALLON, MO
Owner
Attn: Staybridge Suites
Midas O'Fallan SS, LLC
1804 Borman Circle Drive, Ste 100, St. Louis, MO 63146
Phone: (314) 764-4262
Email: kprainito@midashospitality.com
Midas O'Fallan SS, LLC
1804 Borman Circle Drive, Ste 100, St. Louis, MO 63146
Phone: (314) 764-4262
Email: kprainito@midashospitality.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 1.7 - Car door or gate | 1001.2(a)(7) | Correct source of noise from car door. | 6/4/2019 | ||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/21/2021 | ||
A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 6/21/2021 | ||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/21/2021 | ||
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | The in car emergency lighting shall be operational. | 6/21/2021 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency alarm bell shall be operational on auxiliary power. | 6/21/2021 | |
A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | The emergency lowering device (ERU) shall be operational. | 6/21/2021 | |
A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in Section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from its load when the disconnecting means is in the open position. | 6/21/2021 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Remove all non elevator storage from the machine room | 5/23/2022 | ||
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service testing and document on log in machine room | 5/23/2022 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | Document routine maintenance in the maintenance control program | 5/23/2022 | ||
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service and document on log in machine room | 6/28/2024 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Service fire extinguisher in the machine room | 6/28/2024 |