Inspection
Inspection Details
Equipment ID
9968
9968
Inspection Date
2/2/2018
2/2/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
Location
Zieson Construction
1601 Iron St, N Kansas City, MO
Phone: (816) 505-1695
1601 Iron St, N Kansas City, MO
Phone: (816) 505-1695
Owner
TDM Holding
350 SW Farlawn Rd. Suite 100, Topeka, KS 66614
350 SW Farlawn Rd. Suite 100, Topeka, KS 66614
Billing
Attn: TDM Holdings
35 SW Farland Rd. Suite 100, , KS 66614
35 SW Farland Rd. Suite 100, , KS 66614
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | oil packing seals leaking excessively | 6/12/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | no non gfci outlet | 6/12/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | door restrictor not working | 6/12/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | oil collection from cyl. exceeding 5 gals. | 6/12/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | No drain or sump pump in pit | 6/12/2019 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Remove non elevator related items from machine room. | 5/26/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emgergency phone not working. | 7/10/2019 |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 1001.2(c)(2) | No | No | Cartop light not working. | 5/26/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt. of operation displayed | 1/12/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | no drain or sump pump in pit 1061b(3) | 1/12/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | equip. in mach room not connected to elevator operation | 1/12/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | mach. room is being used for storage of non elevator related materials. | 1/12/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt displayed | 1/12/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | non elev related materials in mach.room | 1/12/2026 |
| A17.1-1996 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4.10.1.2 - Protection not functioning | Yes | No | The rupture valve is not performing properly. | 4/1/2026 |