Inspection
Inspection Details
Equipment ID
1224
1224
Inspection Date
5/23/2019
5/23/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Relief Valve Pressure
Na
Na
Slide
Governor Rope Pull
Door Closing Force
Na
Na
External ID
4e14ef2e-cfac-4daa-af68-4e2c8fe23261
4e14ef2e-cfac-4daa-af68-4e2c8fe23261
Location
St. Charles High School
725 N KINGSHIGHWAY ST, SAINT CHARLES, MO
725 N KINGSHIGHWAY ST, SAINT CHARLES, MO
Owner
Attn: St. Charles R-6 School Dist
St. Charles R-6 School Dist
3800 W Clay, SAINT CHARLES, MO 63301
Phone: (636) 443-4880
Email: tringling@stcharlessd.org
St. Charles R-6 School Dist
3800 W Clay, SAINT CHARLES, MO 63301
Phone: (636) 443-4880
Email: tringling@stcharlessd.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. | 5/23/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | 8.6.1.7.5 - The emergency lowering device (ERU) shall be operational. | 8/19/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency light shall be operational. | 1/4/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The alarm bell shall be operational on main and auxiliary power. | 1/4/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/19/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/19/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 8/19/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The "G" level hall push button shall be operational. | 8/19/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 7/22/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit. Water was pumped out of pit but pit floor needs to be cleaned of oil residue. | 7/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The bottom limit switch cover is missing and shall be replaced. | 7/22/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/22/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | The cover for the limit switch assembly in the pit is missing and shall be replaced. | 7/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Per MO State Memorandum 006, oil line from jack head going into tank in machine room is no longer allowed. Oil must go into a container in the pit, no larger than 5 gallons and not permitted to overflow. | 7/22/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it | 7/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Battery lowering unit is not working. | 4/29/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm is not working on battery back up. | 4/29/2026 |