Inspection
Inspection Details
Equipment ID
15909
15909
Inspection Date
5/21/2019
5/21/2019
Inspection Type
Alteration
Alteration
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
320
320
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
8792e2c5-6cca-4d37-93ba-5d49bcb6b5ad
8792e2c5-6cca-4d37-93ba-5d49bcb6b5ad
Location
Hamilton Apartments
956 HAMILTON AVE, SAINT LOUIS, MO
956 HAMILTON AVE, SAINT LOUIS, MO
Owner
Hamilton Apartments
707 SABLE OAKS DR, SOUTH PORTLAND, ME 00000
707 SABLE OAKS DR, SOUTH PORTLAND, ME 00000
Billing
Attn: Preservation Management
956 HAMILTON AVE, SAINT LOUIS, MO 63112-2461
956 HAMILTON AVE, SAINT LOUIS, MO 63112-2461
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit shall be kept clean and dry. | 1/22/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Water and oil shall not be allowed to accumulate on pit floors. | 6/22/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/22/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/22/2022 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 6/22/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Water and oil shall not be allowed to accumulate on pit floors. | 6/22/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/22/2022 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 6/22/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The in-car keyed stop switch shall be tested as required. The key couldn't be located, therefore the switch wasn't tested. | 9/14/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Fire service testing must be documented monthly. | 5/5/2025 |
| A17.1-1996 : Elevators | 2.36 - Hydraulic Cylinders | 302.3 | Yes | Yes | During the inspection, signigicant leakage of hydraulic fluid was observed at the cylinder jack packing glad. The hydraulic jack esperienced a blown packing seal, causing loss of system pressure and uncontrolled movment. Unit has been red tagged and shall be repaired. | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in-car phone, emergency ligh and bell shall be functional. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Pit shall be clean and dry. | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | Yes | No | Fire service phase I and II remain to be tested. |