Inspection
Inspection Details
Equipment ID
14336
14336
Inspection Date
5/14/2019
5/14/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Leo
David Leo
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
00f3cc2c-982e-46e9-98d5-3a8ef69264f2
00f3cc2c-982e-46e9-98d5-3a8ef69264f2
Location
Plaza Frontenac
97 PLAZA FRONTENAC ST, FRONTENAC, MO
97 PLAZA FRONTENAC ST, FRONTENAC, MO
Owner
Attn: Evan DeBrunce
Plaza Frontenac
97 PLAZA FRONTENAC ST, FRONTENAC, MO 63131
Phone: (314) 432-6760
Email: evan.debrunce@brookfieldpropertiesretail.com
Plaza Frontenac
97 PLAZA FRONTENAC ST, FRONTENAC, MO 63131
Phone: (314) 432-6760
Email: evan.debrunce@brookfieldpropertiesretail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | No | No | Replace broken step treads (7.9) and replace broken comb plate on bottom landing (7.7) | 10/3/2018 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(G) | No | No | Bottom left skirt deflector needs repair. | 6/4/2019 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | Yes | Missing step switch at top landing is not working. Repair missing step switch. Red tagged. | 8/4/2021 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | No | Missing step switch at top landing is not working. Repair missing step switch. Red tagged. | 8/12/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete. Need to perform step indexing & comb impact devices on upper landing. Re-inspection required | 5/11/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.4 Escalator Combplates | Yes | No | Comb-step impact devices shall be tested to verify the requirements of 6.1.6.3.13. | 6/1/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.3 Step/Skirt Performance Index | Yes | No | The step/skirt performance index testing required by 8.6.8.15.19 must be performed and witnessed. | 6/1/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | The demarcation lights shall be illuminated when running in automatic operation. | 6/1/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(B) | No | No | The procedure specified by 8.6.11.6.2 shall be utilized when starting an escalator. | 7/6/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | A record of authorized personnel trained as specified in 8.6.11.6.2 shall be kept on the premises where the escalator(s) or moving walk(s) or both is located and shall be available to the authority having jurisdiction. Provide list of trained and authorized personnel to inspection company. | 7/6/2023 |