Inspection Details
Equipment ID
9769
9769
Inspection Date
5/23/2019
5/23/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
UNK
UNK
Governor Rope Pull
200/820
200/820
Door Closing Force
26
26
External ID
1eedbc6b-3778-4433-b492-314c2bebbb7a
1eedbc6b-3778-4433-b492-314c2bebbb7a
Location
Bank of America Tower
100 N BROADWAY, SAINT LOUIS, MO
Phone: (314) 421-0640
100 N BROADWAY, SAINT LOUIS, MO
Phone: (314) 421-0640
Owner
Attn: Hertz Investment Group
Hertz Investment Group
100 N BROADWAY STE 300, SAINT LOUIS, MO 63102
Phone: (314) 421-0640
Email: tsullivan@svncompassrock.com
Hertz Investment Group
100 N BROADWAY STE 300, SAINT LOUIS, MO 63102
Phone: (314) 421-0640
Email: tsullivan@svncompassrock.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Emergency bell shall work | 5/23/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) - | No | No | Need to test fireman's recall. | 11/13/2019 |
| A17.1-1996 : Elevators | 2.17 - Drive machine brake | 1002.3d | Yes | No | Need to do 125% load test. | 8/1/2019 |
| A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 1001.2(e)10 | Yes | No | Need to test car safeties. | 8/1/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Emergency lights shall work. | 2/24/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) - | No | No | Need to test fireman's recall. | 11/13/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Emergency lights shall work. | 2/24/2020 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | Replace hoist ropes - two are stretched to maximum limit. | 2/24/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Repair pit lights that are out. | 2/24/2020 |
| A17.1-1996 : Elevators | 5.10 - Compensating chains, ropes, and sheaves | 1001.2(e)(8) | Yes | No | Shorten compensating ropes. | 1/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light does not work, needs repaired. Re-inspection required | 3/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Need to repair the car door restrictor to work. Re-inspection required | 3/14/2025 |